Sign In | Join Free | My xuijs.com |
|
Brand Name : WONDERY
Model Number : DWL-LNW
Certification : CE
Place of Origin : Jiangsu,China(Mainland)
MOQ : 1 Set/Sets
Price : TO BE ENGOTIATED
Payment Terms : L/C, T/T
Supply Ability : 200 Set/Sets per Year
Delivery Time : 30days
Packaging Details : wooden case suitable for sea transportataion or nude package
Maximum operating temperature : 90℃
nox emission : <30mg/m³
Gas pressure requirements : 2~5Kpa
weight : 410-2100kg
1. Characteristics of cast aluminum heat exchanger
Strong corrosion resistance
Fast heat exchange speed
2. Efficient premixing technology
Fully premixed combustion technology
The optimal ratio of air and gas mixing
Low nitrogen oxide emissions up to 8mg/m ²
Stepless frequency conversion regulation
3. Condensation environmental protection technology
Aluminum condensing heat exchanger
High temperature flue gas liquefaction
Thermal efficiency up to 107%
4. Boiler performance characteristics
The temperature difference between flue gas and boiler return water is 3-5 ° C
Energy saving and efficient
5. System integration and design advantages
Building automation system matching
Control area temperature, domestic hot water, swimming temperature, and solar energy system, etc
Compact design, small footprint
Series model
|
unit
|
LNW360
|
LNW540
|
LNW720
|
LNW1100 | LNW1400 | LNW2100 |
LNW2800
|
|
Rated thermal power |
kw
|
360
|
540
|
720
|
1100
|
1400
|
2100
|
2800
|
|
Maximum operating temperature |
℃
|
90
|
90
|
90
|
90
|
90
|
90
|
90
|
|
nox emission
|
mg/m
|
<30
|
<30
|
<30
|
<30
|
<30
|
<30
|
<30
|
|
Gas pressure requirements
|
Kpa
|
2~5 | 2~5 | 2~5 | 2~5 | 2~5 | 2~5 | 2~5 | |
Power supply requirements
|
power supply
|
V/HZ
|
220/50
|
380/50
|
380/50
|
380/50
|
380/50
|
380/50
|
380/50
|
Distribution power
|
W
|
700
|
900
|
1100
|
1800 |
3500
|
5300
|
6500
|
|
Operating conditions at (50-30) ℃
|
thermal efficiency
|
%
|
107.1
|
107.5
|
107.5
|
107.4
|
107.3
|
107.4
|
107.3
|
Exhaust gas temperature
|
℃
|
48
|
45
|
46
|
47
|
49
|
47
|
48
|
|
Gas consumption
|
m³/h
|
33.6
|
50.2
|
67.0
|
102.4
|
130.5
|
195.5
|
268
|
|
Operating conditions at (80-60) ℃ |
thermal efficiency
|
%
|
98.1
|
98.4
|
98.3
|
98.2
|
98.1
|
98.3
|
98.3
|
Exhaust gas temperature |
℃
|
69
|
66
|
67
|
68
|
69
|
68
|
68
|
|
Gas consumption
|
m³/h
|
36.7
|
54.9
|
73.2
|
112.0
|
142.7
|
213.8
|
292.8 | |
size parameter |
long
|
mm
|
1456
|
1620
|
1842
|
2280
|
2628
|
2850
|
3300
|
wide
|
mm
|
650
|
850
|
850
|
910
|
910
|
1310
|
1700
|
|
high
|
mm
|
1220
|
1474
|
1474
|
1746
|
1746
|
2750
|
2600
|
|
weight |
kg
|
410
|
480
|
620
|
830
|
960
|
1500
|
2100
|
|
interface size
|
outlet
|
mm
|
DN50
|
DN100
|
DN100
|
DN100
|
DN100
|
DN200
|
DN200
|
Return water outlet |
mm
|
DN50
|
DN100
|
DN100
|
DN100
|
DN100
|
DN200
|
DN200
|
|
Gas interface |
mm
|
40
|
40
|
40
|
50
|
50
|
65
|
65
|
|
Chimney diameter
|
Φmm
|
200
|
250
|
250
|
305
|
305
|
420
|
420
|
Note: The calorific value of natural gas is calculated at 8600 kcal/m ³; Technical parameters may change due to continuous product improvement, and factory data shall prevail.
![]() |
High Efficiency Energy Saving 350-2800 KW Gas Hot Water Boiler With 15-100% Stepless Variable Frequency Regulation Images |